Liquid-cooled racks
Racks delivered with manifolds, hoses and power distribution fitted, ready to connect to the aisle piping network.

- W × D × H
- 600 × 1,200 × 2,000mm
- Integrated manifold
- DN50
System role
Where it sits in the system.
Houses the IT equipment and terminates the secondary loop at the server through an integrated rack manifold.
IT loop
01 / 09 · Heat source
GPU / CPU
By others
Processor heat flux sets every downstream requirement: coolant supply temperature, flow per server and allowable pressure drop.
02 / 09 · Chip-to-liquid heat transfer
Cold plate
Interface
Coolant passes through a plate mounted on the processor. Its flow and pressure-drop figures are the design inputs for the manifold and CDU.
03 / 09 · In-rack distribution
Rack manifold
LINKWAVE scope
A stainless manifold in each rack divides supply flow between servers and collects the return through 12 mm EPDM hoses.
View productSecondary loop
04 / 09 · Local coolant distribution
Rack / in-row CDU
LINKWAVE scope
Where load is distributed or facility water is unavailable, a CDU at the rack or row conditions and circulates coolant close to the IT equipment.
05 / 09 · Technology cooling system
Secondary cooling loop
LINKWAVE scope
Sanitary-grade stainless aisle piping carries treated water between the racks and the CDU. Typical supply and return: 40 / 55 °C.
View product06 / 09 · Loop isolation and control
Centralized CDU
LINKWAVE scope
A plate heat exchanger separates the IT loop from facility water. Dual variable-speed pumps hold flow and pressure. Reference units: 500 kW and 2.5 MW.
View productPrimary loop
07 / 09 · Facility water system
Primary cooling loop
LINKWAVE scope
Facility water carries heat from the CDUs to the heat-rejection plant. Water quality is managed by make-up, dosing and filtration on this side.
08 / 09 · Primary circulation
Primary-side pump station
LINKWAVE scope
Skid-built pumps with variable-frequency drives, storage, make-up and dosing. 125 kW to 2.5 MW, 10–250 m³/h.
View product09 / 09 · Heat rejection
Dry cooler / cooling tower / chilled water
Interface
Three reference arrangements: isolated CDU with chilled water; isolated CDU with cooling tower and pump station; direct-connected CDU with dry cooler and online purification.
Heat travels from chip to heat rejection. Select a stage for detail.
Engineering highlights
Manifold, hoses and switchgear integrated at the factory.
- Integrated manifold
- DN50 round or ST50 square stainless manifold with 12 mm EPDM hoses to each server position.
- Top-mounted switchgear
- Power switching is located at the top of the rack, clear of the coolant connections.
Technical specifications
Specifications
SI units, with US customary equivalents where useful. Values are for the reference configurations shown; project units are sized to the load.
Mechanical
| Dimensions (W × D × H) | 600 × 1,200 × 2,000 mm23.6 × 47.2 × 78.7 in |
|---|
Hydraulic
| Pipe material | SS304 / SS316L, sanitary grade |
|---|---|
| Manifold | DN50 round pipe or ST50 square pipe |
| Flexible hose | EPDM, 12 mm |
Electrical
| Supply | 3-phase, 380–480 V, 50/60 Hz |
|---|---|
| Switch | Top-mounted |
Environmental
| Ambient temperature | −25 to 40 °C−13 to 104 °F |
|---|---|
| Relative humidity | 5–95 % |
| Altitude | ≤ 3,000 m≤ 9,840 ft |
Sizing this system for your load?
Send the heat load, flow and temperature requirements. An engineer will respond with a configuration and the open questions.