AI Data Centers
Direct-to-chip cooling for GPU halls, from manifold to heat rejection.
Direct-to-chip loops served by centralized CDUs, with variable-speed pumping that follows the load.

Engineering challenge
GPU racks reject more heat than air can remove, and the load swings with every training run.
- Heat density beyond air
- Accelerator racks concentrate heat at the chip. Removing it with air alone requires airflow and fan power that a hall cannot practically provide.
- Load that moves
- Training and inference workloads change rack heat output quickly. Coolant flow and supply temperature have to follow without overshoot.
- Two cooling systems in one hall
- Cold plates remove most of the heat, but not all of it. The remainder still needs air cooling, coordinated with the liquid loop.
LINKWAVE response
How the system is built.
- 01Centralized CDU on an isolated loop
- A plate heat exchanger separates the technology loop from facility water. Reference units are rated at 500 kW and 2.5 MW, with a typical 40 / 55 °C inlet and outlet.
- 02Variable-frequency pumping
- Dual pumps on variable-frequency drives adjust flow to the real-time load. Heat-rejection fan speed follows load and ambient temperature.
- 03Liquid and air in one scope
- Where residual heat needs air cooling, in-row units, power monitoring and environmental monitoring can be delivered with the liquid system, as in the Nanjing reference.
System architecture
Where the work happens in the loop.
The same chain applies to every project. What changes is where capacity, redundancy and control are placed.
IT loop
01 / 09 · Heat source
GPU / CPU
By others
Processor heat flux sets every downstream requirement: coolant supply temperature, flow per server and allowable pressure drop.
02 / 09 · Chip-to-liquid heat transfer
Cold plate
Interface
Coolant passes through a plate mounted on the processor. Its flow and pressure-drop figures are the design inputs for the manifold and CDU.
03 / 09 · In-rack distribution
Rack manifold
LINKWAVE scope
A stainless manifold in each rack divides supply flow between servers and collects the return through 12 mm EPDM hoses.
View productSecondary loop
04 / 09 · Local coolant distribution
Rack / in-row CDU
LINKWAVE scope
Where load is distributed or facility water is unavailable, a CDU at the rack or row conditions and circulates coolant close to the IT equipment.
05 / 09 · Technology cooling system
Secondary cooling loop
LINKWAVE scope
Sanitary-grade stainless aisle piping carries treated water between the racks and the CDU. Typical supply and return: 40 / 55 °C.
View product06 / 09 · Loop isolation and control
Centralized CDU
LINKWAVE scope
A plate heat exchanger separates the IT loop from facility water. Dual variable-speed pumps hold flow and pressure. Reference units: 500 kW and 2.5 MW.
View productPrimary loop
07 / 09 · Facility water system
Primary cooling loop
LINKWAVE scope
Facility water carries heat from the CDUs to the heat-rejection plant. Water quality is managed by make-up, dosing and filtration on this side.
08 / 09 · Primary circulation
Primary-side pump station
LINKWAVE scope
Skid-built pumps with variable-frequency drives, storage, make-up and dosing. 125 kW to 2.5 MW, 10–250 m³/h.
View product09 / 09 · Heat rejection
Dry cooler / cooling tower / chilled water
Interface
Three reference arrangements: isolated CDU with chilled water; isolated CDU with cooling tower and pump station; direct-connected CDU with dry cooler and online purification.
Heat travels from chip to heat rejection. Select a stage for detail.
Heat-rejection arrangements
- Isolated CDU + chilled water
- The CDU exchanges heat with an existing chilled-water system. Suited to facilities that already run a chiller plant.
- Isolated CDU + cooling tower + pump station
- A primary-side pump station, including a dosing unit, circulates facility water between the CDU and a cooling tower.
- Direct-connected CDU + dry cooler
- The CDU connects directly to a dry cooler, with online purification maintaining water quality in the single loop.
Planning a liquid-cooled facility?
Send the load, rack density and facility constraints. An engineer will respond with an architecture and the open questions.